AL-114 110v
 
 
 
 
  ELECTRICAL CHARACTERISTICS

-Supply: 110V CA 50/60Hz.
-Supply: 115 V. c.a. 50/60 Hz.(it depends on your order)
-Power consumption: 3,5 VA Max.
-Maximum intensity in relay contacts: 16A (supported charge)
-Type of drill: 3 Electrodes
-Voltage in tips of drill (empty state): 15 V a.c.
-Force average through of the drill: 40 uA.
 
 
 

 

 
  .Critical resistence:

- Min. Level:  Enable:140 Kohm
                    Disable:230 Kohm
- Max. Level: Enable: 130 Kohm
                    Disable: 230 Kohm
- Time-out:   Enable: 0,3 sec.
                    Disable: 0,3 sec.
- Time-out of security: 170 sec.
 
 

REFRIGERACIÓN BARCINOVA, S.A.
C/. Consorts Sans Bernet, 46
  08032 - Barcelona (SPAIN )
  Teléfono: (+ 34) (+ 34) 93 407-02-45
  Fax.: (+ 34) 93 407-02-45